Ready-to-Use Chemical Solution | |
Temperature | up to 160°F |
Pressure | 35 to 100 PSI |
Flow | 4 GPM @ 40 PSI |
Supply Line | 1/2" Min |
Compressed Air | up to 6 CFM |
Hose/Pipe | 1" & 3/4" ID |
Nozzle | HV Entryway Spreader (2 - use both) |
Requirements
Ready-to-Use Chemical Solution | |
Temperature | up to 160°F |
Pressure | 35 to 100 PSI |
Flow | 4 GPM @ 40 PSI |
Supply Line | 1/2" Min |
Compressed Air | up to 6 CFM |
Hose/Pipe | 1" & 3/4" ID |
Nozzle | HV Entryway Spreader (2 - use both) |
Overview
Safety & Operational Precautions
To Install (refer to diagram on next page)
Illustration on Page 1 shows overall system setup.
Run a
common 1/2" ID compressed air supply line from the Satellite Controller
to each Satellite . The size of the airline may need to be 3/4"
depending on the distance and number of Satellite Entryway Foamers being
installed. You will need up to 6 CFM at 60 PSI per station. If in
doubt, oversize the airline. You can use short 3/8" tubing to connect the main airline to each Satellite.
To Operate
The Satellite Entryway Foam Sanitizer is equipped with an air ball valve the unit can be shut off or isolated at any time by closing the air ball valve. The unit will not operate when the air ball valve is closed, regardless of the central Satellite Controller settings. Do not use the air ball valve to control air flow. This ball valve must be fully open for the unit to operate correctly.
For initial set up and testing you can temporarily, connect a separate compressed air supply to the unit.
Testing Procedure when unit is connected to a Timed or PLC Jazz Satellite Controller:
Unit Flow Rates | |
---|---|
PSI | GPM |
35 | 3.74 |
40 | 4.00 |
50 | 4.47 |
60 | 4.90 |
70 | 5.29 |
80 | 5.66 |
90 | 6.00 |
100 | 6.32 |
Troubleshooting Guide |
---|
Problem | Possible Cause / Solution | |
---|---|---|
Startup | Maintenance | |
A) Foam surges. B) Foam output too wet. C) Foam output too dry. D) Unit doesn't come on when switch is turned on. E) Unit comes on and runs continuously. F) Unit comes on but no solution through solenoid. | 1, 2, 3, 4, 6, 7, 8, 9, 10, 11 2, 3, 4, 6, 7, 8, 9, 10, 11 1, 5 11, 12 11 12 |
13, 15, 16 13, 14, 15, 16 13, 14 15 |
Possible Cause / Solution | |
---|---|
Startup | Maintenance |
|
|
PREVENTIVE MAINTENANCE: When the unit will be out of service for extended periods, run water through the system to flush the chemical and help prevent chemical build-up. |